Intuchem passive fire protection homepage

Installation Information

871


Insulated Pipe Sleeve Installation Guide

 

Insulated Pipe Sleeve installation

The acoustic insulated intumescent pipe sleeve is an effective product for the fire stopping of pipe penetrations e.g. plumbing pipe and metallic pipes whilst maintaining similar thermal and acoustic properties as standard mineral fibre insulation. These properties ensure compliance to water bye laws and building regulations for hot and cold water pipes and heating systems.

In a fire situation the sleeve expands to fill the available space between the pipe and the penetration. In the case of plastic pipes the sleeve will crush and close off the pipe forming a solid char and preventing the passage of fire and smoke to the adjacent compartment.

Suitable for use on: Copper 12mm- 160mm | Mild steel 22mm - 160mm | Polybutylene 12mm - 28mm | PVC 55mm - 160mm. Matix shows pipe/construction material combinations tested.

Pipe

Blockwork Wall

Solid Floor

Mineral Batt

Plasterboard Wall

12MM Copper

 

160MM Copper

 

22MM Mild Steel

 

160MM Mild Steel

 

12MM Polybutylene

28MM Polybutylene

55MM PVC

82MM PVC

110MM PVC

160MM PVC


1

Carefully cut the pipe sleeve to the required length

Cut pipe sleeve  to length

2

If necessary make single slit along sleeve length to allow fitting around installed

Slit sleeve

3

Fit sleeve around pipe and reseal the cut with repair tape

Fit sleeve to pipe and seal cut with tape

4

Slide sleeve along pipe and into cavity and tape sleeve to existing insulation if required

Locate sleeve into place

Please note : for irregular holes or gaps of greater than 15mm around the pipe sleeve fill with mortar,mastic or similar.smaller gaps can be filled with Intuchem Sealant if required

The information in this publication is accurate to the best of the knowledge of Intuchem Ltd.

LEGAL:
As part of our policy of ongoing improvements, we reserve the right to modify, alter or change product specifications without giving notice. Product illustrations are representations only. All information contained in this document is provided for guidance only, and as Intuchem Ltd has no control over the installation methods of the products, or of the prevailing site conditions, no warranties expressed or implied are intended to be given as to the actual performance of the products mentioned or referred to, and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given of products mentioned or referred to herein.