FIRE GRILLES:
60 Minute Rated
For use in Walls & Doors
LOUVERED COVER PLATES:
Steel Louvered Plate
SAA or White Finish
|
|
Fire Grilles (intumescent) |
Product Description:
FIRE GRILLES:
Intuchem Intumescent air transfer grille is a durable ventilation
grille which is easily mounted in Fire doors, & solid walls, and
can provide in excess of 60 Minutes fire rating.
Suitable for mounting up to 1,000mm (1m) from floor
level.
Comprising of an intumescent slated core within a galvanized steel frame
with vermin proof mesh fitted to both faces.
The design allows a free area of 80% approximately -
see our table below for guidance
Maximum grille size is 600mm² or equivalent area, or use a combination
of grilles up to a maximum size of 1500 x 1000mm.
Circular grilles are available in 100, 125, 150, 200, 225, 250 and 300mm
diameter sizes.
LOUVERED COVER PLATES:
We can also supply steel Louvered Cover Plates matched
to the appropriate grille dimensions.
Intuchem Steel Louvered Cover Plates are manufactured
from a robust fabricated 2Oswg mild steel, with a free flow are of approx
70%. Available in Satin Anodised Aluminium.
Features:
Fire Grilles 60 minute rated
Tested to BS476: Part 22:
80% free area
Vermin proof mesh
For use in doors & walls
|

|
|
|
Free Air flow Table: Fire Grilles
|
| Size
in mm. |
| |
100 |
150 |
200 |
225 |
250 |
300 |
350 |
400 |
450 |
500 |
550 |
600 |
100 |
80cm2
|
120cm2
|
160cm2
|
180cm2
|
200cm2
|
240cm2
|
280cm2
|
320cm2
|
360cm2
|
400cm2
|
440cm2
|
480cm2
|
150 |
|
180cm2 |
240cm2 |
270cm2 |
300cm2 |
360cm2 |
420cm2 |
480cm2 |
540cm2 |
600cm2 |
660cm2 |
720cm2 |
200 |
|
|
320cm2
|
360cm2
|
400cm2
|
480cm2
|
560cm2
|
640cm2
|
720cm2
|
800cm2
|
880cm2
|
960cm2
|
225 |
|
|
|
405cm2
|
450cm2
|
540cm2
|
630cm2
|
720cm2
|
810cm2
|
900cm2
|
990cm2
|
1080cm2
|
250 |
|
|
|
|
500cm2
|
600cm2
|
700cm2
|
800cm2
|
900cm2
|
1000cm2
|
1100cm2
|
1200cm2
|
300 |
|
|
|
|
|
720cm2
|
840cm2
|
960cm2
|
1080cm2
|
1200cm2
|
1320cm2
|
1440cm2
|
350 |
|
|
|
|
|
|
980cm2
|
1120cm2
|
1260cm2
|
1400cm2
|
1540cm2
|
1680cm2
|
400 |
|
|
|
|
|
|
|
1280cm2
|
1120cm2
|
1600cm2
|
1760cm2
|
1920cm2
|
450 |
|
|
|
|
|
|
|
|
1620cm2
|
1800cm2
|
1980cm2
|
2160cm2
|
500 |
|
|
|
|
|
|
|
|
|
2000cm2
|
2200cm2
|
2400cm2
|
550 |
|
|
|
|
|
|
|
|
|
|
2420cm2
|
2640cm2
|
600 |
|
|
|
|
|
|
|
|
|
|
|
2880cm2
|
|
Calculations made using 80%(approx) free air flow - not allow
for the effects of fitting face plates or other gille coverings |
|
Fire
Grille
Size in mm. |
Face
plate dimensions to match Fire Grille size |
|
|
| 100.00
|
150.00
|
200.00
|
250.00
|
300.00
|
350.00
|
400.00 |
450.00 |
500.00 |
600.00
|
| 100.00 |
102x102
|
152x102
|
203x102
|
254x102
|
305x102
|
356x102 |
406x102 |
457x102 |
508x102 |
610x102 |
| 150.00 |
|
152x152
|
203x152
|
254x152
|
305x152
|
356x152 |
406x152 |
457x152
|
508x152
|
610x152 |
| 200.00 |
|
|
203x203
|
254x203
|
305x203
|
356x203 |
406x203 |
457x203
|
508x203 |
610x203 |
| 250.00 |
|
|
|
254x254
|
305x254
|
356x254 |
406x254 |
457x254
|
508x254 |
610x254
|
| 300.00 |
|
|
|
|
305x305
|
356x305
|
406x305 |
457x305 |
508x305 |
610x305 |
| 350.00 |
|
|
|
|
|
356x356 |
406x356 |
457x356 |
508x356 |
610x356 |
| 400.00 |
|
|
|
|
|
|
406x406 |
457x406 |
508x406
|
610x406 |
| 450.00 |
|
|
|
|
|
|
|
457x457 |
508x457 |
610x457 |
| 500.00 |
|
|
|
|
|
|
|
|
508x508 |
610x508 |
| 600.00 |
|
|
|
|
|
|
|
|
|
610x610 |
| Intuchem Steel Louvered Cover
Plates have a free flow are of approx 70%. |
|
|
Other Information:
View Installation or Safety (COSHH) Datasheet on this page.
|
|
LEGAL:
As part of our policy of ongoing improvements, we reserve the right to
modify, alter or change product specifications without giving notice.
Product illustrations are representations only. All information contained
in this document is provided for guidance only, and as Intuchem Ltd has
no control over the installation methods of the products, or of the prevailing
site conditions, no warranties expressed or implied are intended to be
given as to the actual performance of the products mentioned or referred
to, and no liability whatsoever will be accepted for any loss, damage
or injury arising from the use of the information given of products mentioned
or referred to herein.
The above information to the best of our knowledge is true and accurate
and based upon current test data and is supplied for your guidance only.
Customers should satisfy themselves to the suitability of the product
in its intended use and no guarantee is given or implied since the conditions
of actual use are beyond our control. Intuchem Ltd disclaim any liability
for loss, damage or other expense arising from the use of information,
data or products mentioned or referred to and reserve the right to change
any details or specifications without notice.
|
|